Panasonic FV-1115VQL1 Exhaust Fan Specifications

ENERGY STAR PD #2378303 · Bathroom/Utility Room · Qualified 2021-05-21
Verified Specification Summary

The Panasonic FV-1115VQL1 (WhisperCeiling DC) moves 150 CFM at 0.1 in. w.g. (146.2 CFM at 0.25 in. w.g.), omits a published 0.1-inch sone rating, and delivers 11.7 CFM/W efficacy, sizing bathrooms up to 146 sq ft (8-ft ceilings) under IRC M1505 and ASHRAE 62.2. Verify ducted airflow at 0.25 in. w.g., rigid galvanized pipe diameter, roof damper termination, and IRC M1505 / ASHRAE 62.2 room sizing requirements alongside Panasonic FV-1115VQL1 Exhaust Fan Specifications before installation.

Airflow @ 0.1" / 0.25"
150 / 146.2 CFM
Noise @ 0.1"
Unpublished
Efficacy Rank
11.7 CFM/W (#103/1,145)
Static Retention
97.5% @ 0.25"
Motor Draw
12.8 W (4.7 kWh/yr)
Duct & Tier
6 in. diameter · Standard
Flush matte white bathroom exhaust fan grille mounted cleanly in a finished bathroom ceiling
Insulated 4-inch galvanized attic exhaust duct vented cleanly to an exterior damper cap.

What does Panasonic FV-1115VQL1 vs. 1,145-Model ENERGY STAR Benchmarks show?

Panasonic FV-1115VQL1 (EPA filing PD #2378303) omits a published 0.1-inch sone acoustic rating in its current Bathroom/Utility Room certification record.

Strong static stability: under 0.25 in. w.g. duct backpressure it holds 146.2 CFM out of 150 CFM (97.5% retention, 9.8 pts higher retention than the 87.7% median). The 6-inch collar lowers air friction across longer attic runs—do not neck down to 3-inch flex.

Panasonic maintains 92 active ENERGY STAR blowers; FV-1115VQL1 (series: WhisperCeiling DC) (PD #2378303) gained qualification on 2021-05-21. Lighting kit: Yes. At 11.7 CFM/W (#103 of 1,145, top 9.0% of 1,145 rated models, more efficient than 91.0% of rated models, 7.0 CFM/W more efficient than the 4.7 CFM/W median), electrical draw computes to 12.8 watts, about 4.7 kWh/yr (~$0.75/yr at $0.16/kWh) for 1 hr/day shower timers or 112.1 kWh/yr (~$17.94/yr) continuously. Closest competing matches include Loren Cook Company GCVF 100 (127.0 CFM) and KORA SBF160DC-MS (161.6 CFM).

How does duct geometry alter Panasonic FV-1115VQL1 static pressure?

Smooth 6 in. diameter galvanized ducts terminated outdoors preserve rated CFM at 0.25 in. w.g., whereas sagging 3-in attic flex chokes airflow below IRC M1505 minimums.

Bathroom Exhaust Fan Static Pressure and Duct Geometry Schematic Comparison showing smooth 4-inch or 6-inch rigid galvanized duct preserving airflow at 0.25 in. w.g. to an exterior roof cap versus choked 3-inch flex duct venting improperly into attic insulation. Target: Rigid 4-in / 6-in Outdoors Damper Roof Cap Fan <= 1.0 Sone Retains ~82%+ CFM @ 0.25 in. w.g. Smooth galvanized steel Defect: 3-in Flex / Attic Vent Mold & Frost Inside Attic Builder 3.0 Sone Choked static drop <50 CFM
Architectural duct layout illustrating IRC M1505 / ASHRAE 62.2 exterior termination and 0.25 in. w.g. static pressure preservation.

Which certified test ratings apply to Panasonic FV-1115VQL1?

Review EPA ENERGY STAR ducted airflow, sound sones, electrical efficacy, and collar fit for Panasonic FV-1115VQL1 alongside residential IRC M1505 and ASHRAE 62.2 ventilation benchmarks.

Verified specifications and code or agency threshold checks
ParameterVerified ValueReference Standard / Note
Manufacturer / Brand Share Panasonic (92 models) ENERGY STAR Certified Partner
Model Number & Series FV-1115VQL1 / WhisperCeiling DC PD ID 2378303 (Qualified 2021-05-21)
Duct Connection 6 in. diameter Use smooth rigid metal outdoors
IRC M1505 (>=50 CFM) Check PASS (146.2 CFM) DOE/PNNL BASC (ASHRAE 62.2 / IRC M1505)
Acoustic Suite (<=1.0 Sone) Unpublished Fleet median 1.0 sones
Integrated Lighting Yes Verify switched neutral wiring

How much bathroom area can Panasonic FV-1115VQL1 ventilate safely?

Sizing outputs below convert Panasonic FV-1115VQL1 tested CFM and motor watts into maximum 8-ft and 9-ft ceiling footprints plus annual kWh energy totals.

Bathroom sizing limits and annual kWh draw for Panasonic FV-1115VQL1
Bathroom Duty / ScenarioMax Room Size / OutputStatic & Cost Basis
Standard Bath (8-ft Ceiling)Up to 146 sq ft1 CFM/sq ft @ 146.2 CFM
Tall Bath (9-ft Ceiling)Up to 129 sq ftScaled +12.5% volume factor
Walk-In Tub / Steam (+50 CFM)Up to 96 sq ftSubtracts 50 CFM moisture reserve
Intermittent Use (1 hr/day)4.7 kWh/yr (~$0.75/yr)12.8 W x 365 hrs / 1,000
Continuous 24/7 ASHRAE 62.2112.1 kWh/yr (~$17.94/yr)12.8 W x 8,760 hrs / 1,000

Which ENERGY STAR fans match Panasonic FV-1115VQL1 closely?

Comparable certified models below pair similar airflow capacity, acoustic sone ratings, and motor efficacy so homeowners can cross-check contractor substitutions.

Nearest peers matched by CFM airflow, acoustic sones, and motor efficacy
Peer Brand & ModelCFM (0.1" / 0.25")Sones (Delta)EfficacyDuct
Loren Cook Company GCVF 100 127 / N/A CFM 1.7 sones 11.1 CFM/W 5.94 in. diameter
KORA SBF160DC-MS 161.6 / N/A CFM 1.3 sones 8.7 CFM/W 4 in. diameter
Broan QTXE110150DC 150 / 147.8 CFM Unpublished 11.0 CFM/W 6 in. diameter
Broan QTXE110150DC=QTXEDCH with QTXE110150DCF 150 / 147.8 CFM Unpublished 11.0 CFM/W 6 in. diameter
Broan QTXE110150DCL 150 / 147.8 CFM Unpublished 11.0 CFM/W 6 in. diameter

Will Panasonic FV-1115VQL1 clear IRC M1505 in your bathroom?

Enter your room floor area and ceiling height below to verify whether Panasonic FV-1115VQL1 satisfies ASHRAE 62.2 and residential IRC M1505 airflow rules locally.

Which bath layouts should avoid specifying Panasonic FV-1115VQL1?

Match Panasonic FV-1115VQL1 directly against your home's framing clearances, hot-water tank recovery rate, and local municipal inspection tolerances.

Limitations & Who Should Skip

  • Steam or walk-in tub room > 96 sq ft requiring +50 CFM boost
  • Existing attic run relies on >15 ft of 3-inch corrugated flex

Best-Fit Homeowner Profiles

  • Best for: Bathroom floor <= 146 sq ft with 8-ft ceilings (129 sq ft at 9-ft height)
  • Optimal use: Exterior run uses smooth rigid metal matched to 6 in. diameter

What key rules and numbers govern Panasonic FV-1115VQL1?

Answers below summarize primary U.S. agency datasets, statutory limits, and residential IRC, IPC, or NEC building rules affecting Panasonic FV-1115VQL1.

What happens to Panasonic FV-1115VQL1 CFM when vented through elbows and roof caps?

Against realistic 0.25 in. w.g. system resistance, Panasonic FV-1115VQL1 moves unlisted 0.25 in. w.g. backpressure figures compared to its 50 CFM free-discharge spec, avoid sharp flex bends on its 6 in. diameter collar.

Where does Panasonic FV-1115VQL1 sit on acoustic comfort for senior homeowners?

Measuring an unpublished 0.1-in sone rating, Panasonic FV-1115VQL1 produces audible mechanical sound suited better to utility baths or half-baths than quiet primary suites, avoiding the harsh hum common in older 3.0-to-4.0 sone bath fans.

What does Panasonic FV-1115VQL1 cost in annual electricity for intermittent vs continuous duty?

Operating at ENERGY STAR airflow verification, running Panasonic FV-1115VQL1 1 hour daily uses ~low intermittent draw, whereas 24/7 ASHRAE 62.2 continuous exhaust consumes ~continuous ASHRAE duty across 8,760 annual hours at your local kWh rate.

Can Panasonic FV-1115VQL1 pair with an enclosed walk-in tub or steam shower?

Enclosed soaking basins and walk-in tubs add a +50 CFM moisture reserve under DOE/PNNL sizing guidance. Subtracting 50 CFM from Panasonic FV-1115VQL1's 50 CFM leaves capacity for insufficient floor area (<20 sq ft), requiring a higher-CFM unit.

What duct diameter and termination rules apply when installing Panasonic FV-1115VQL1?

Panasonic FV-1115VQL1 features a 6 in. diameter collar. Mechanical codes require venting insulated rigid ducting straight outdoors via a roof or wall damper cap, never into open attic framing or soffits.

How does ceiling height above 8 feet change Panasonic FV-1115VQL1's room sizing?

Standard 1 CFM per sq ft charts assume 8-foot ceilings. A 9-foot ceiling adds 12.5% room volume, reducing Panasonic FV-1115VQL1's safe coverage footprint from 50 sq ft to 44 sq ft.

What bathroom square footage can Panasonic FV-1115VQL1 ventilate under ASHRAE 62.2?

Rated at 50 CFM effective capacity (unlisted 0.25 in. w.g. backpressure figures), Panasonic FV-1115VQL1 covers up to 50 sq ft with standard 8-ft ceilings and clears the 50 CFM intermittent code benchmark.

Where does Panasonic FV-1115VQL1 run out of capacity in residential remodeling?

Homeowners with baths exceeding 50 sq ft, 9-foot ceilings above 44 sq ft, or walk-in tubs requiring +50 CFM moisture reserve should step up rather than undersizing with Panasonic FV-1115VQL1.